May 3, 20176 min read
OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements
Industry:
Solution:
In some cases, OSHA requires employers to have fire extinguishers at work, and in other cases, employers will choose to provide fire extinguishers. In either scenario, if a company will place portable fire extinguishers in the workplace, it’s important to know OSHA requirements covering mounting fire extinguishers and fire extinguisher placement as well as as OSHA fire extinguisher signage requirements.
We’ll cover each of those three issues–fire extinguisher mounting height, fire extinguisher placement, and fire extinguisher signage requirements–in this article.
Vector EHS Management Softwareempowers organizations – from global leaders to local businesses – to improve workplace safety and comply with environmental, health, and safety regulations.
Learn more about how our software can save you valuable time and effort in recording, tracking, and analyzing your EHS activities.
Learn more about how we can help:
- Incident Management Software→
- EHS Inspection Software→
- Key Safety Metrics Dashboard→
- Learning Management System (LMS)andOnline Training Courses→
- Mobile Risk Communication Platform
Download ourEHS Management SoftwareBuyer’s Guide.
OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements
Let’s look at the OSHA requirements for each of these issues.
OSHA Fire Extinguisher Placement
The issue of fire extinguisher placement requirements from OSHA begins with cases in which OSHA requires the employer to have portable fire extinguishers and/or the employer decides to.
If portable fire extinguishers will be present,1910.157(c)(1)lays down the first requirement:
The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.
So the key issue above is “readily accessible to employees without subjecting the employees to possible injury.” Please note this is assuming the employer allows employees to use the extinguishers.
The next concern about fire extinguisher placement is the distance the employee has to travel to reach an extinguisher. This is based on the type of extinguisher (and/or the Class of fire it can put out), as listed below.
Placement of portable fire extinguishers for Class A fires
便携式灭火器必须放置,这样the travel distance for employees to any extinguisher is 75 feet or less. — see1910157(d)(2)
In addition, here’s what an OSHA Evacuation Plans and Procedures eTool (on theExtinguisher Placement and Spacingpage) says regarding extinguishers for Class A fires:
The National Fire Protection Association (NFPA) recommends that locations such as offices, classrooms, and assembly halls that contain mainly Class A combustible materials have one 2-A extinguisher for every 3,000 square feet. [Standard for Portable Fire Extinguishers (NFPA 10(2010), Table 6.2.1.1, Fire Extinguisher Size and Placement for Class A Hazards)].
OSHA requires that all employees have access to an extinguisher within 75 feet travel-distance. [29 CFR 1910.157(d)(2)]
NOTE: Uniformly spaced standpipe systems or hose stations connected to a sprinkler system for emergency use can be used instead of Class A portable fire extinguishers, if they meet the respective requirements of29 CFR 1910.158or29 CFR 1910.159, provide total coverage of the area to be protected, and employees are trained at least annually in their use. [29 CFR 1910.157(d)(3)]
Placement of portable fire extinguishers for Class B fires
便携式灭火器必须放置,这样the travel distance for employees to any extinguisher is 50 feet or less.– see1910.157(d)(4)
In addition, here’s what an OSHA Evacuation Plans and Procedures eTool (on theExtinguisher Placement and Spacingpage) says regarding extinguishers for Class B fires:
Hazard | Extinguisher | Spacing |
---|---|---|
Light (Low) Small amounts of flammable liquids used for copy machines, art departments, etc., that are stored safely and kept in closed containers. |
5-B | 30 feet |
Light (Low) Small amounts of flammable liquids used for copy machines, art departments, etc., that are stored safely and kept in closed containers. |
10-B | 50 feet |
Ordinary (Moderate) The total amount of flammable liquids are present in greater amounts than expected under low-hazard locations. This can include garages, workshops, or support service areas. |
10-B | 30 feet |
Ordinary (Moderate) The total amount of flammable liquids are present in greater amounts than expected under low-hazard locations. This can include garages, workshops, or support service areas. |
20-B | 50 feet |
Extra (High) Locations where flammable liquids are present and used in large quantities. This includes areas used for storage, production, woodworking (finishing), vehicle repair, aircraft and boat servicing, or where painting, dipping, and coating, operations are performed with flammable liquids. |
40-B | 30 feet |
Extra (High) Locations where flammable liquids are present and used in large quantities. This includes areas used for storage, production, woodworking (finishing), vehicle repair, aircraft and boat servicing, or where painting, dipping, and coating, operations are performed with flammable liquids. |
80-B | 50 feet |
OSHA notes they’ve adapted this information above from “Standard for Portable Fire Extinguishers,”NFPA 10(2010), Table 6.3.1.1, Fire Extinguisher Size and Placement for Class B Hazards
Placement of portable fire extinguishers Class C fires
Here, OSHA says “The employer shall distribute portable fire extinguishers used for Class C hazards on the basis of the appropriate pattern for the existing Class A or Class B hazards.”– see1910.157(d)(5)
Placement of portable fire extinguishers for Class D fires
OSHA has a little more to say for Class D fires. Here’s what they say: “The employer shall distribute portable fire extinguishers or other containers of Class D extinguishing agent for use by employees so that the travel distance from the combustible metal working area to any extinguishing agent is 75 feet (22.9 m) or less. Portable fire extinguishers for Class D hazards are required in those combustible metal working areas where combustible metal powders, flakes, shavings, or similarly sized products are generated at least once every two weeks.”– see1910.157(d)(6)
Placement of portable fire extinguishers for Class K fires
The placement of extinguishers for Class K fires isn’t directly covered the 1910 OSHA regulation, but is addressed in an OSHA Evacuation Plans and Procedures eTool (on theExtinguisher Placement and Spacingpage). Here’s what that eTool says:
Locations where potential fire hazards from combustible cooking media (vegetable or animal oils and fats) exist must install Class K extinguishers at a maximum travel distance of 30 feet. [NFPA 10, Standard for Portable Fire Extinguishers. See Section 6.6, Installations for Class K Hazards]
Americans with Disabilities Act & Fire Extinguisher Placement Issues
Although we’re focusing on OSHA regulations concerning fire extinguishers, remember that you may also have to consider things like local building codes,NFPArequirements (checkNFPA 10), and even theAmericans with Disabilities Act (ADA).
According to the ADA, if an object is mounted to the wall (like fire extinguishers often are), and their leading edges are located between 27 inches and 80 inches above the finished floor, the mounted object can protrude no more than four inches into walkways, corridors, passageways, or aisles. This is at least one reason why you’ll often see fire extinguishers inside recessed cabinets within a wall instead of mounted on the wall and sticking out into a traffic way.
OSHA Fire Extinguisher Mounting Height Requirements
Now let’s turn our attention to fire extinguisher mounting height requirements.
If you go back to1910.157(c)(1), you’ll see all the OSHA regulation has to say on the issue of mounting height:
The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.
So the key in there is to make sure “they are readily accessible to employees without subjecting the employees to possible injury.”
BUT, OSHA has anEvacuation Plans and Procedures eToolwith a page dedicated tofire extinguisher mounting and placing, and that page says:
To prevent fire extinguishers from being moved or damaged,they should be mounted on brackets or in wall cabinets with the carrying handle placed 3-1/2 to 5 feet above the floor. Larger fire extinguishers need to be mounted at lower heights with the carrying handle about 3 feet from the floor.
OSHA Fire Extinguisher Signage Requirements
And finally, let’s turn our attention to OSHA’s fire extinguisher signage requirements.
As we did before, let’s go back to1910.157(c)(1). Here’s what OSHA says about signage requirements for fire extinguishers:
The employer shall provide portable fire extinguishers and shall mount, locate and identify them so that they are readily accessible to employees without subjecting the employees to possible injury.
注意没什么特定的标志。所有the 1910 regulation says is the portable fire extinguishes should be “identified.”
So here, you’re best off following good-old common sense. Place a sign or something similar that makes it easy for people to know where an extinguisher is/extinguishes are. Consider placing it so it can be seen well from up close, at a distance, and from different angles. And make sure there’s nothing that obstructs a person’s view of the extinguisher and/or the sign (such as a pile of boxes, machinery, or an open door).
Additional Articles About Fire Extinguishers That May Interest You
In addition to this article, you may find the following articles related to fire safety and fire extinguishers helpful:
- OSHA Fire Extinguisher Safety Training Requirements
- How to Use a Fire Extinguisher – Step by Step Guide
- Types of Fire Extinguishers – Which One To Buy
- How to Pass an OSHA Fire Extinguisher Inspection
Finally, you may want to consider ouronline fire extinguisher safety training video. We’ve included a short sample of it immediately below.
The Wrap Up: OSHA Fire Extinguisher Mounting Height, Placement & Signage Requirements
We hope this answered some of your questions about fire extinguisher placement, signage, and mounting requirements. Please remember that fires are a real hazard, that every year people die from fires unnecessarily, and that with proper precaution andsafety trainingwe can all make sure a lot more people make it home from work alive and well.
For more details, download our FREE RISK-BASED SAFETY MANAGEMENT GUIDE.
Risk Management Guide for Safety
Learn to use risk-management approaches for safety and health management.
Download Now